Honeywell CC-TAIX01 Product Introduction & Technical Parameters
Temperature Parameters:
Operating Temperature: -20°C to +70°C
Storage Temperature: -40°C to +85°C
Relative Humidity: 5%–95% non-condensing

Input:
Power Input: 24V DC (via system backplane)
Signal Input: 16-channel analog inputs (12 single-ended, 4 differential)
Supported Input Types: 0–5V, 1–5V, 0.4–2V, 4–20mA
Input Isolation: ≥2500V RMS (field-to-logic)
Input Impedance: Voltage: >1 MΩ; Current: 250 Ω
Resolution: 16-bit A/D converter
Accuracy: ±0.1% full-scale (at 25°C)
Output:
Digital Output: Process data to C300 controller via system bus
Communication: HART protocol support for smart field devices
Status Output: Channel health, fault, and communication LEDs
Features:
Designed for Honeywell C300 and Experion PKS DCS platforms
16 configurable analog input channels with HART compatibility
High accuracy (±0.1% FS) and 16-bit resolution
Galvanic isolation (≥2500V RMS) for noise immunity
High common-mode rejection (CMRR ≥80dB)
Industrial-grade construction for harsh environments
Plug-and-play IOTA design for easy installation and replacement
CE, UL, and RoHS compliant
LED indicators for power, status, and fault diagnostics
Low power consumption and compact form factor